ÀÏâÝÑÏíã-220 1x800 ÒÓ Ó 31.3-00214534-061:2008 |
Power cables with aluminium conductor, XLPE-insulated, with copper screen, lead-sheathed, with outer sheath of polymer composition, flame retardant |
Technical cable requirements correspond to IEC 62067 |
|
|
|
Cables are used for laying: |
• in places, where small mechanical impacts on cable are possible, including tensile forces |
• in premises, tunnels, ducts, mines, dry soil and outdoor under shelter |
• single laying |
|
|
|
It is possible to manufacture cables with extruded semiconductor layer along outer sheath. Order entry example: |
ÀÏâÝÑÏíã-Ï–220 1x800/95 ÒÓ Ó 31.3-00214534-061:2008 |
An extruded semiconductor layer along outer sheath ensures the correct testing of cable line with sections of underground laying in polymer pipes. To learn more. |
|
|
|
It is possible to manufacture cables with an integrated fiber-optic module. Order entry example: |
ÀÏâÝÑÏíã-220 1x800/95 (ÎÌ) ÒÓ Ó 31.3-00214534-061:2008 |
In conjunction with the DTS system, the integrated fiber-optic module can act as a distributed cable line temperature sensor. To learn more. |
|
|
|
It is possible to manufacture cable with sealed conductor. Order entry example: |
ÀÏâÝÑÏíã-220 1x800/95 (ã) ÒÓ Ó 31.3-00214534-061:2008 |
|
|
|
Fire safety code in accordance with ÄÑÒÓ 4809:2007: ÏÁ101122000 |
Products of this mark meet the requirements: |
• single wire cable flame retardance |
• toxicity class Tk1 of the combustion products of nonmetallic elements (toxicity index from 13 up to 40 g/m3) |
• class ÄÒê1 on smoke-forming ability by smouldering of non-metallic elements (coefficient of smoke formation from 50 to 500 m2/kg) |
• class ÄÏê2 on smoke-forming ability by combustion (minimum luminous flux more than 60 %) |
• corrosive class Êê2 of combustion products of non-metallic elements (the number of halogen hydrides less than 150 mg/g, pH more than 4.3, specific conductivity less than 10 µS/mm) |