31.3-00214534-017-2003
Single-core power cables with aluminium conductor, flame-retardant, with XLPE, aluminium-wire armoured, with PVC compound outer sheath, with low smoke and gas emission
Due to non-magnetic armour, cables operate at AC
Technical cable requirements correspond to IEC 60502-2
Cables are used for laying:
in places, where small mechanical impacts on cable are possible, including tensile forces
in premises, tunnels, ducts, mines, dry soil and outdoor under shelter
in bunches
at sites, where low smoke and gas emission are required (NPP, subway, large industrial facilities, high-rise buildings, etc.)
It is possible to manufacture cables with an integrated fiber-optic module.
Order entry example:
-6 1x50/16 () 31.3-00214534-017-2003
In conjunction with the DTS system, the integrated fiber-optic module can act as a distributed cable line temperature sensor. To learn more.
It is possible to manufacture cable with single-wire conductor.
Order entry example:
-6 1x50/16 () 31.3-00214534-017-2003
It is possible to manufacture cable with sealed conductor.
Order entry example:
-6 1x50/16 () 31.3-00214534-017-2003
It is possible to supply of three stranded single-core cables.
Order entry example:
3x-6 1x50/16 31.3-00214534-017-2003
Fire safety code in accordance with 4809:2007: 122121000
Products of this mark meet the requirements:
single wire cable flame retardance
bunched cable flame retardance category A
toxicity class Tk2 of the combustion products of nonmetallic elements (toxicity index from 40 up to 120 g/m3)
class 1 on smoke-forming ability by smouldering of non-metallic elements (coefficient of smoke formation from 50 to 500 m2/kg)
class 2 on smoke-forming ability by combustion (minimum luminous flux more than 60 %)
corrosive class 1 of combustion products of non-metallic elements (the number of halogen hydrides less than 150 mg/g, pH less than 4.3, specific conductivity more than 10 S/mm)