ÀÏâÝîÏíã-HF(ê)-15 3x300
ÒÓ Ó 31.3-00214534-058:2007
Three-core power cables with aluminium conductors, flame-retardant and halogen-free, with XLPE, collective screen and polymer compound outer sheath
Technical cable requirements correspond to IEC 60502-2
Cables are used for laying:
• in premises, tunnels, ducts, mines, dry soil and outdoor under shelter
• at sites, where low smoke and corrosive gas emission are required (NPP, subway, large industrial facilities, high-rise buildings, etc.)
• single laying
It is possible to manufacture cables with extruded semiconductor layer along outer sheath.
Order entry example:
ÀÏâÝîÏíã-HF(ê)-Ï–15 3x300/70 ÒÓ Ó 31.3-00214534-058:2007
An extruded semiconductor layer along outer sheath ensures the correct testing of cable line with sections of underground laying in polymer pipes. To learn more.
It is possible to manufacture cables with an integrated fiber-optic module.
Order entry example:
ÀÏâÝîÏíã-HF(ê)-15 3x300/70 (ÎÌ) ÒÓ Ó 31.3-00214534-058:2007
In conjunction with the DTS system, the integrated fiber-optic module can act as a distributed cable line temperature sensor. To learn more.
It is possible to manufacture cable with sealed conductors.
Order entry example:
ÀÏâÝîÏíã-HF(ê)-15 3x300/70 (ã) ÒÓ Ó 31.3-00214534-058:2007
It is possible manufacturing of cables in versions (A) and (B), flame-retardant when laying in bunches
Fire safety code in accordance with ÄÑÒÓ 4809:2007: ÏÁ102122000
Products of this mark meet the requirements:
• single wire cable flame retardance
• toxicity class Tk2 of the combustion products of nonmetallic elements (toxicity index from 40 up to 120 g/m3)
• class ÄÒê1 on smoke-forming ability by smouldering of non-metallic elements (coefficient of smoke formation from 50 to 500 m2/kg)
• class ÄÏê2 on smoke-forming ability by combustion (minimum luminous flux more than 60 %)
• corrosive class Êê2 of combustion products of non-metallic elements (the number of halogen hydrides less than 150 mg/g, pH more than 4.3, specific conductivity less than 10 µS/mm)